i.Node series - The i.Node series products are network I/O devices that have adopted the LonWorks flatform (ANSI/EIA/CEA 709.1) and are used exclusively for LonWorks that is a standard for the open distributed control in the industrial automation control sector.
LonWorks-based controlling network can be built by connecting various digital and analog sensors and actuators to the iNode series products, receiving values from the sensors, and controlling the actuators.
i.Node TDI4DO4
Product Features
4 digital input channels and 4 digital output 4 channels are provided
The system¡¯s stability and scalability have been enhanced due to the intelligent distributed control method
Easy to install and maintain as the system is based on a network.
Interactive communication, multi-targeting and multi-controlling are made possible
Digitalized I/O processing due to intelligent devices
Easy to install and manage due to the LNS plug-in program. A user interface is supported.
Product Specifications
Item
Description
Processor Type
FT3150
FT5000
Transceiver Type
FT-X1 or FT-X3
Processor Clock
10MHz
Memory
32K Flash Memory, 2K EEPROM
Comm. Media
TP(Twisted Pair Line)
POWER
15~30 VAC/VDC
Protocol
ANSI/EIA/CEA 709.1 Lon Talk Protoco
ANSI/EIA/CEA 709,3 Twisted Pair Line
Digital Input
Dry-contact, 30VDC Max (0~9V:ON, 9~ :OFF)
Digital Output
Relay Output, 3A Max
Dimension
92(W) x 96(H) x 82(D) m
Operation Temp./Humidity
-10~50¡É, 0~85%
Mounting
Wall mount type or Din Rail Base Plate type
Plug-in
Plug-In type
Functions
Digital Input
Select among the digital input detection functions: Direct, One shot, Togle, Pulsed, Override
Digital Output
Set the digital output control functions: Direct, One shot, Togle, PWM, One pulse, Preset, Override
Analog Input
Select among the analog input detection functions : Sensor type and range setting, Filter setting, NV range & offset setting
User table setting, Upper limit/Lower limit alarm setting, Override
Analog Outpt
Set the digital output control functions: Preset table, Input range setting, Scaling, Offset, Override
Loop
Set the PID control function: P/I/D factor setting, and P_bias, Deadband, and I limit setting
Compare
Input NV comparison function: Equal, Not Equal, Greater than equal, Less, And, Or, Or not
Multi Function
Input NV comparison function: Equal, Not Equal, Greater than equal, Less, And, Or, Or not
Not equal,Greater than equal,Less,Selector,Higher,lower,Add
Sub,Mul,Div,Enthalpy
Analog Control
Input NV comparison and operation functions: Equal, Not equal, Greater than equal, Less, Select, Higher, lower
Logic, Encoder, On time, and Counter functions based on Input NV
General Function Block